Buffer tank

When it is necessary to plan a buffer space to absorb the fast pressure variations, especially when the solenoids are situated after a B type regulator, the piping volume from the regulator to the consumption point has to be at least equal:
- in BP (21, 27, 37 mbar) to 1/500 of the regulator nominal flow
- in MPA (300 mbar) to 1/1000 of the regulator nominal flow

Designation

Fitting double female

2 transition fittings pressure gauge

Ref. Chuchu

Tank 10 L

1"1/4

1/4"

2420-010

Tank 25 L

1"1/2

1/4"

2420-025

Tank 50 L

1"1/2

1/4"

2420-050

Maximal use pressure: 500 mbar
Horizontal or vertical assembly - Delivered with caps on both transition fittings